engineering recuitment BMC Sub Engineer Mock Test 2024 Refrigeration and Air Conditioning Air Conditioning Bypass Factor
Air at 25°C DBT and 80% RH is passed over a cooling coil whose surface temperature is 10°C which is below DPT of the air. If the air temperature coming out of the cooling coil is 15°C, then the bypass factor of the cooling coil is:
1
0.56
2
0.33
3
0.76
4
0.87
5
0.66