A three-phase feeder having a resistance of 3 Ω and a reactance of 10 Ω supplies a load of 2 MW at 0.85 lagging power factor. The receiving end voltage is maintained at 11 kV by means of a static condenser drawing 2.1 MVAR from the line. The sending end voltage is
1
11 kV
2
10 kV
3
12 kV
4
13 kV