A power system consists of 300 buses out of which 20 buses are connected with generators, 25 buses are the ones with controlled reactive power support and 15 buses are the ones with fixed shunt capacitors. All other buses are load buses. It is proposed to perform a load flow analysis using Newton-Rapson method. The size of the Newton-Rapson Jacobian matrix is
1
553 × 553
2
540 × 540
3
555 × 555
4
554 × 554