engineering recuitment GATE EE 2023-24 Test Series Power Systems Protective Relays Differential Relays
A three phase, 2 pole, 11 kV 10000 kVA alternator has neutral earthed through a resistance of 7 Ω. The machine has current balance protection which operates upon out of balance current that exceed 20% of full load. The % of winding protected against earth fault is _______
Neglect the % reactance of generator winding.1
11.57%
2
88.43%
3
79.21%
4
21.79%