For the vapor absorption refrigeration system, the temperature of the evaporator is given as -12°C. The ambient temperature is given as 35°C. The actual COP is 30% of the maximum COP of the VARs. The load on the VARs is given as 24 tonne. The heat is supplied to the generator by condensing steam at 0.275 MPa and 78% quality. The steam flow rate required for this purpose will be ________ kg/min.

Take Tsat = 130.60°C, hfg = 2172.4 kJ/kg at 0.275 MPa

Enter numerical value using the virtual keypad. Round off where necessary.