A 3-phase generator rated at 110 MVA, 11 kV is connected through circuit breaker to a transformer. The generator having direct axis sub transient reactance 19%, transient reactance X’ = 26% and synchronous reactance 130%. The generator is operating at no load and rate voltage when 3 phase short circuit occurs between the breakers and the transformer. The magnitude of initial symmetrical RMS current in the breakers will be

1
4.44 kA
2
22.20 kA
3
30.39 kA
4
38.45 kA
5
10 kA

Sponsored

hivanix.in

Visit

This quiz is brought to you by hivanix.in

🌐 Web App Development

Quick Navigation