A balanced three phase delta connected load is supplied by a balanced 3-phase, 400 V supply. The phase current is 10 A at a 0.8 power factor lagging. The total reactive power absorbed by the load is

1
7.2 kVAR
2
2.4 kVAR
3
3.2 kVAR
4
9.6 kVAR