engineering recuitment HPCL Junior Executive 2025 Mock Test Refrigeration and Air Conditioning Refrigeration Cycles and Devices Vapour Compression (V-C) Cycle
In an ideal vapor-compression refrigeration cycle the refrigeration effect is 80kJ/kg of refrigerant flow. The COP is 4. If the flow of the refrigerant is 2 kg/s, the heat rejected in the condenser is
1
50 kW
2
100 kW
3
150 kW
4
200 kW