A three-phase generator rated 11 kV, 20 MVA has a solidly grounded neutral. Its positive, negative and zero sequence reactances are 60%, 25% and 15% respectively. The value of reactance that should be placed in the generator neutral such that the current for single line to ground fault does not exceed the rated current.
1
0.94 pu
2
0.54 pu
3
0.67 pu
4
0.47 pu