The open circuit test in a 100 kVA, 2000/200 V, 50 Hz, single phase transformer gives 200 V, 90 A, 5 kW on low voltage side. Core loss and magnetizing components of the current approximately are respectively
1
9.0 A, 89.5 A
2
12.5 A, 88.7 A
3
25.0 A, 86.5 A
4
30.0 A, 84.9 A
5