A load of 15 MW at a power factor of 0.8 lagging can be delivered by a three-phase transmission line having conductors each of resistance 1 Ω per kilometer. The voltage at the receiving end is to be 132 kV and the loss in the transmission is to be 5%. The length of the transmission line is _____ (in km)
Enter numerical value using the virtual keypad. Round off where necessary.