engineering recuitment GATE EE 2023-24 Test Series Power Systems Transmission and Distribution Transient Analysis on Long Transmission Lines
The sending end rated voltage of a 3ϕ, 300 km transmission line is 400 kV. It has A = D = 0.98∠0°, B = 20∠90° Ω and C = 0.1411∠90° , then characteristic impedance of the line is:
Enter numerical value using the virtual keypad. Round off where necessary.