engineering recuitment GATE EE 2023-24 Test Series Power Systems Fault Analysis Line To Ground Fault
A generator rated 100 MVA, 20 kV has Xd” = X1 = X2 = 20% and X0 = 5%. Its neutral is grounded through a reactor of 0.32 Ω. The generator is operating at rated voltage without load and is disconnected from the system when a single line to ground fault occurs at its terminals. The sub transient current in the faulted phase is ______ (in kA)
Enter numerical value using the virtual keypad. Round off where necessary.