For an office building the outdoor design conditions are 25°C DBT and 0.01 humidity ratio. The supply air state is 15°C DBT and 0.007 humidity ratio. If the supply air flow rate is 1000 m3/min then office sensible and office latent heat loads are respectively

1
408 kW and 400 kW
2
408 kW and 150 kW
3
312 kW and 100 kW
4
204 kW and 150 kW