engineering recuitment GATE ME 2023-24 Test Series Refrigeration and Air Conditioning Air Conditioning Properties of Moist Air (Psychrometric Properties)
Air flowing at 100 m3/min at a dry bulb temperature of 313K (PS = 0.0738 bar) and 25% relative humidity is made to pass through an adiabatic humidifier. The air comes out at 298 K dry bulb temperature (PS = 0.0317 bar) and a relative humidity of 0.635. If the atmospheric pressure is 1 bar, then calculate the water carried by air in kg/min.
Enter numerical value using the virtual keypad. Round off where necessary.