In an air-conditioning plant, air enters the cooling coil at 27°C. The coil surface temperature is -5°C. If the bypass factor of the unit is 0.4, the air will leave the coil at:
1
5.6°C
2
7.8°C
3
9.2°C
4
11.2°C