A generator delivers power of 1 p.u. to an infinite bus through a purely reactive network. The maximum power that could be delivered by the generator is 2.0 p.u. A three-phase fault occurs at the terminals of the generator which reduces the generator output to zero. The fault is cleared after tc seconds. The original network is then restored. The maximum swing of the rotor angle (δ) of the generator is found to be δmax = 120 electrical degrees. The value of cos δ at time t = tc is

1
0.285
2
0.471
3
0.512
4
0.352